Web-Based Configuration & Control...
ContactAgent's built-in web server allows
you to configure all monitoring modes and alarm
thresholds easily and intuitively. Digital (contact)
inputs can be individually set up to make alarms on
state changes, and the 'normal' and 'alarm' states
can be user-defined. analog inputs can be bracketed
by alarm thresholds.
|
User-defined Analog Scaling...
Each analog input can have individual user-defined
scale factors applied. Thus, an input that varies
from say, 10-12VDC can be made to display in
user-defined scaleable units, such as "5.7-9.5 Amps"
|
Fail-Safe Relay Outputs...
The ROM modules controllable Form-C relay output
contacts are mechanically latched, which means that
the contact state will not change during a loss of
system power
|
SNMP Interface...
ContactAgent's industry-standard SNMP interface
gives you complete control to monitor and manage
installations and equipment without locking you into
proprietary software. most SNMP compliant manager
software can easily be made to work with
ContactAgent
|
|
Specifications
>>Documents<<
Master Unit
Number Inputs:
8 digital (contact closure)
Input Electrical: 1 ma
max closed-switch current
Number Outputs: 2 Form-C
contact sets; state not
preserved on power failure
Output Electrical: 60V max; 5A
Slave Unit Interface: RS-485/RJ-45 connector
Operating Power: 5 VDC from
supplied wall-mount
power supply
Network Interface: 10/100 Ethernet
Protocols:
TCP/IP;SNMP;HTTP;SMTP;
DHCP;TFTP
Size:
8"W x 4.25"D x 1.5"H (rack
mountable)
RIM Module
Number Inputs:
6 digital/analog (user-definable)
Analog Measurements: +/- 12VDC; 0-8VRMS
Temperature Sensor: Included; +/-2deg from -40C
to +80C
Humidity Sensor:
Optional; +/-3% accuracy from
20%RH to 80%RH
Max # Units:
4 RIM's per Master Unit
Interface to Master: RS-485 on RJ-45 connector;
powered via daisy-chain
AC Line Measurement: 90-140VAC
ROM Module
Number
Outputs: 4 Form-C; latching
Output Electrical: 60V max; 5A
Temperature Sensor: Included; +/-2deg from -40C
to +80C
Humidity Sensor:
Optional; +/-3% accuracy from
20%RH to 80%RH
Max # Units:
4 ROM's per Master Unit
Interface to
Master: RS-485 on RJ-45 connector;
powered via daisy-chain
Accessories:
-Rack-mount
bracket (RK-1)
-Humidity Measurement (RIM/ROM only) |