Web-Based Configuration & Control...
ContactAgent's built-in web server allows you to configure all monitoring modes and alarm thresholds easily and intuitively. Digital (contact) inputs can be individually set up to make alarms on state changes, and the 'normal' and 'alarm' states can be user-defined. analog inputs can be bracketed by alarm thresholds.
 

User-defined Analog Scaling...

Each analog input can have individual user-defined scale factors applied. Thus, an input that varies from say, 10-12VDC can be made to display in user-defined scaleable units, such as "5.7-9.5 Amps"
 

Fail-Safe Relay Outputs...

The ROM modules controllable Form-C relay output contacts are mechanically latched, which means that the contact state will not change during a loss of system power
 

SNMP Interface...

ContactAgent's
industry-standard SNMP interface gives you complete control to monitor and manage installations and equipment without locking you into proprietary software. most SNMP compliant manager software can easily be made to work with ContactAgent
 

Specifications                           >>Documents<<

Master Unit

Number Inputs:        8 digital (contact closure)
Input Electrical:       1 ma max closed-switch current
Number Outputs:      2 Form-C contact sets; state not
                             preserved on power failure
Output Electrical:     60V max; 5A
Slave Unit Interface: RS-485/RJ-45 connector
Operating Power:      5 VDC from supplied wall-mount
                             power supply
Network Interface:    10/100 Ethernet
Protocols:               TCP/IP;SNMP;HTTP;SMTP;
                             DHCP;TFTP
Size:                      8"W x 4.25"D x 1.5"H (rack
                             mountable)

RIM Module

Number Inputs:          6 digital/analog (user-definable)
Analog Measurements: +/- 12VDC; 0-8VRMS
Temperature Sensor:   Included; +/-2deg from -40C
                              to +80C
Humidity Sensor:        Optional; +/-3% accuracy from
                              20%RH to 80%RH
Max # Units:             4 RIM's per Master Unit
Interface to Master:   RS-485 on RJ-45 connector;
                              powered via daisy-chain
AC Line Measurement:  90-140VAC

ROM Module

Number Outputs:      4 Form-C; latching
Output Electrical:     60V max; 5A
Temperature Sensor:   Included; +/-2deg from -40C
                              to +80C
Humidity Sensor:        Optional; +/-3% accuracy from
                              20%RH to 80%RH

Max # Units:             4 ROM's per Master Unit

Interface to Master:   RS-485 on RJ-45 connector;
                              powered via daisy-chain

 

Accessories:

-Rack-mount bracket (RK-1)
-Humidity Measurement (RIM/ROM only)

--